Electrical Engineering

Voltage Drop Calculator & Cable Power Loss Estimator

Estimate voltage drop, delivered voltage, conductor resistance, power loss and energy cost from transparent electrical assumptions.

Free engineering reference tool

Voltage-drop estimate

Enter circuit and conductor assumptions, then calculate a local engineering estimate. Results include the electrical path, delivered voltage, conductor loss, energy cost and cable-area comparison.

Voltage drop
Awaiting inputs
Delivered voltage
Awaiting inputs
Cable power loss
Awaiting inputs
Annual energy loss
Awaiting inputs

Cable path

SupplySupply
Cable runOne-way length · Area · CurrentLost
LoadLoad

Supply, cable run, then load. Lost across the cable path.

Voltage proportion

What this voltage drop calculator does

A voltage drop calculator answers one practical question: how much voltage is lost between the supply and the load because the cable itself has resistance. This tool estimates that loss for DC two-wire, single-phase AC and balanced three-phase AC circuits, then shows the knock-on effects - the voltage actually delivered to the load, the percentage drop, the power wasted as heat in the conductor, and the energy and cost of that loss over a year.

Every input is visible and editable. You supply the supply voltage, the load current, the one-way cable length, the conductor cross-sectional area in square millimetres (mm²), the conductor material and the circuit type. The tool converts metres or feet to metres, converts mm² to square metres, applies R = rho x L / A for the conductor resistance, and then applies the formula that matches your circuit type. Nothing is sent to a server and no network request is made.

How voltage drop is calculated

Conductor resistance comes first. With bulk-material resistivity rho in ohm metres, one-way length L in metres and cross-sectional area A in square metres, the resistance of a single conductor is R = rho x L / A. Copper and aluminium reference values are held locally and versioned so the calculation is traceable.

  • DC two-wire: Delta V = I x 2R, because the current travels out along one conductor and back along the other.
  • Single-phase AC: Delta V = 2 x I x R x power factor for a resistive estimate, or 2 x I x L x (R cos phi + X sin phi) when you enter conductor resistance and reactance per kilometre.
  • Balanced three-phase AC: Delta V = sqrt(3) x I x R x power factor for a resistive estimate, with cable power loss calculated as 3 x I²R per phase conductor.
  • Delivered voltage is the supply voltage minus the drop, and the percentage drop is the drop divided by the supply voltage.
  • Cable power loss is I²R across the whole circuit path, and the annual energy loss multiplies that by operating hours per day and operating days per year.

Cable area, resistance and voltage drop reference

The table below is derived from the same resistivity constants the calculator uses, at the 20 °C reference temperature. It gives the resistance of one conductor in ohms per kilometre, and the indicative voltage drop per amp of load current for every 10 m of single-phase and balanced three-phase circuit at unity power factor. Multiply by your own current and length to make a first-pass estimate, then use the calculator itself for the exact result.

Conductor resistance and indicative voltage drop per amp, derived from the same bulk-material resistivity constants the calculator uses (20 °C reference, copper 1.724e-8 Ω·m, aluminium 2.826e-8 Ω·m).
Cable area (mm²)Copper (Ω/km)Aluminium (Ω/km)Single-phase drop per A per 10 mThree-phase drop per A per 10 m
0.534.480056.52000.6896 V0.5972 V
0.7522.986737.68000.4597 V0.3981 V
117.240028.26000.3448 V0.2986 V
1.511.493318.84000.2299 V0.1991 V
2.56.896011.30400.1379 V0.1194 V
44.31007.06500.0862 V0.0747 V
62.87334.71000.0575 V0.0498 V
101.72402.82600.0345 V0.0299 V
161.07751.76630.0216 V0.0187 V
250.68961.13040.0138 V0.0119 V
350.49260.80740.0099 V0.0085 V
500.34480.56520.0069 V0.0060 V
700.24630.40370.0049 V0.0043 V
950.18150.29750.0036 V0.0031 V
1200.14370.23550.0029 V0.0025 V
1500.11490.18840.0023 V0.0020 V
1850.09320.15280.0019 V0.0016 V
2400.07180.11780.0014 V0.0012 V

Worked examples

The examples below are calculated with the same engine that runs the tool, so the published numbers cannot drift away from the calculator's own behaviour. Take the 230 V single-phase example: a 16 A load, 20 m of 2.5 mm² copper and a power factor of 0.9. A 2.5 mm² copper conductor has a resistance of 0.13792 ohm over 20 m, so the drop is 2 x 16 x 0.13792 x 0.9 = 3.972 V, the delivered voltage is 226.03 V and the cable loses 70.62 W as heat.

Notice how quickly the numbers move. The same 16 A load over 100 m of the same conductor drops 19.86 V, which is more than 8 % of a 230 V supply and would leave many loads below their working voltage. Doubling the conductor to 5 mm² roughly halves the drop, because resistance falls in proportion to area.

Worked examples calculated with the same engine the tool uses, at the stated inputs.
ExampleInputsVoltage dropDropDelivered voltageCable power loss
12 V DC accessory circuitDC two-wire, 12 V, 5 A over 4 m on 1.5 mm² copper0.46 V3.83 %11.54 V2.3 W
24 V battery systemDC two-wire, 24 V, 20 A over 8 m on 10 mm² copper0.552 V2.3 %23.45 V11.03 W
230 V single-phase loadsingle-phase AC, 230 V, 16 A over 20 m on 2.5 mm² copper3.972 V1.73 %226.03 V70.62 W
400 V balanced three-phase loadbalanced three-phase AC, 400 V, 32 A over 35 m on 10 mm² copper2.843 V0.71 %397.16 V185.36 W
Long cable runsingle-phase AC, 230 V, 10 A over 120 m on 16 mm² aluminium4.239 V1.84 %225.76 V42.39 W

Choosing a cable size

  • Start from the load current and the distance, then use the calculator to test candidate conductor sizes against the percentage drop you need.
  • A small conductor raises the drop but also raises the power loss and running cost, so the cheapest cable on paper is often the most expensive to run.
  • Parallel conductors are supported: the tool divides the effective conductor resistance by the number of parallel runs per pole.
  • Where you have manufacturer data, enter resistance and reactance per kilometre in impedance mode instead of relying on bulk-material resistivity.

What the results mean

  • Voltage drop is the difference between the supply voltage and the voltage at the load terminals.
  • The percentage drop is measured against the supply voltage, so it stays comparable between a 12 V accessory circuit and a 400 V three-phase supply.
  • Cable power loss is energy converted to heat in the conductor. It is not the load's consumption - it is waste.
  • Annual loss cost uses the electricity price and duty cycle you enter, so it is an estimate at your own tariff rather than a market average.
  • The cable-size comparison shows what the same circuit would do with neighbouring common conductor sizes.

Limitations

  • Results depend on the values you enter, and they are estimates rather than a design or compliance determination.
  • Conductor construction may differ from ideal bulk-material reference values, so a real cable's resistance can be higher than the resistive estimate.
  • AC impedance may require manufacturer data. In resistive mode reactance is ignored, which matters on longer runs and at higher currents.
  • Conductor temperature affects resistance. Use the temperature adjustment option when the cable runs hot.
  • Cable current capacity (ampacity), protective-device coordination, installation method and regulatory compliance are not assessed.
  • Harmonic, transient and unbalanced three-phase conditions are outside the model.

Frequently asked questions about voltage drop calculator & cable power loss estimator

How do I calculate voltage drop?

Calculate the resistance of one conductor with R = rho x L / A, multiply by the current, and use the factor for your circuit: 2 x I x R for a DC two-wire path, 2 x I x R x power factor for single-phase AC, and sqrt(3) x I x R x power factor for balanced three-phase AC. The voltage drop calculator does these steps for you and shows the full working.

What is the voltage drop formula for a single-phase circuit?

For a resistive estimate, Delta V = 2 x I x R_conductor x power factor. The factor of two is the outgoing and return conductor. When you enter the cable's resistance and reactance per kilometre instead, the tool uses Delta V = 2 x I x L x (R cos phi + X sin phi).

How do I calculate voltage drop for a three-phase circuit?

For a balanced three-phase load the resistive estimate is Delta V = sqrt(3) x I x R_conductor x power factor, where R_conductor is the resistance of one phase conductor over the one-way run. Cable power loss for the same circuit is 3 x I²R per phase conductor.

What cable size do I need for a given voltage drop?

Enter your load current and cable run length, then test candidate conductor areas in the calculator and compare the percentage drop. The tool estimates voltage drop only - it does not assess cable current capacity, protective-device coordination, installation method or regulatory compliance, so the result is a starting point for a design decision rather than an approval.

Does this calculator support AWG?

No. It works in square millimetres (mm²) and in ohms per kilometre. AWG is a separate conductor-sizing standard used in North America, so an AWG figure cannot be read as a millimetre value directly. Use the impedance mode and enter your cable's resistance per kilometre if you have the manufacturer's data.

Why is my voltage drop different from the manufacturer's figures?

The resistive estimate uses bulk-material resistivity values for copper and aluminium at 20 °C. Real conductors are not perfectly homogeneous, and resistance rises with temperature, so a warm or long run will show a higher drop than a reference table. Enter the manufacturer's resistance per kilometre in impedance mode for a closer estimate.

Does the calculator work out the cable's current-carrying capacity?

No. Ampacity depends on installation method, ambient temperature, insulation type, grouping and local wiring rules, none of which the tool models. Use a current-capacity reference alongside the voltage drop result, and have the final design checked against the regulations that apply to your installation.

Is this suitable for compliance or installation decisions?

No. It is a transparent reference calculation for technical and educational use. It does not certify a design, and it does not replace a qualified assessment against the wiring rules that apply where the cable will be installed.